Description
Product properties
- 2-wire integrated transmitter
- 25 GHz (K-band) measuring signal
- Non-contact level metering
- Accuracy up to ±3 mm
- Measuring range up to 23 m
- 99-point linearisation
- Plastic housing
- Horn, planar or parabolic antenna
- Stainless steel or plastic encapsulated sensor
- Explosion-proof models
- Where IP68 is needed
Applications
- Level measurement of liquids, emulsions and other chemicals
- Food and beverage
- Chemical industry
- Oil industry
- Water / wastewater industry
| Power supply: | 20 – 36 V DC |
|---|---|
| Ambient temperature: | -20 °C … +60 °C |
| Process temperature: | -30 °C … +100 °C |
| Pressure: | -1 bar – 3 bar |
| Output: | 4 – 20mA, HART |
| Process connection: | 1 ½”, 2″ or flanges or sanitary |
| Protection: | IP68 |
| Approvals: | ATEX, IEC Ex, FCC, INMETRO |
| Brochure | |
| EN | PiloTREK |
| Technical drawing | |
| WPM-140 | |
| WPM-14N | |
| WPM-150 | |
| WPM-15N | |
| WPP-140 | |
| WPP-150 | |